The PiBridge is the internal system bus (backplane bus) of the RevPi. It connects the RevPi base module with the RevPi I/O Modules and the RevPi Gateways.

Via the PiBridge:

  • The RevPi Base modules from the RevPi Core and RevPi Connect series can be connected to up to ten expansion devices, both mechanically and electrically. See also Rules for the Arrangement of Devices.

  • Devices are automatically detected and configured.

  • Process data is submitted cyclically.

  • RevPi Gateways are connected via dedicated Ethernet channels.

The device configuration is carried out via PiCtory.

Mounting and Connecting #

The devices are connected by plugging them mechanically together on the DIN rail.

Connecting Expansion Modules

Caution
Damage to the device due to installation under voltage supply

While the RevPi device is connected to a power source, no other devices may be connected or disconnected, as this may cause damage to the devices.

▷ Do not connect the power supply until all other devices are connected correctly.

▷ Switch off the power supply before disconnecting a device from the system.

Caution
Damage to the device due to different grounding

▷ Refer all connections to the same system ground.

▷ Connect external voltage inputs or outputs with different grounding externally.

Caution
Damage to the devices due to mix-up of the plug connectors

▷ Only connect RevPi I/O modules and RevPi gateways to the system via the black PiBridge plug connectors.

▷ Only connect RevPi Con M-Bus and RevPi Con CAN to the system via the gray ConBridge plug connectors.

▷ Make sure that all devices are disconnected from their power supplies.

▷ Mount all RevPi devices next to each other on the DIN rail.

▷ Connect the RevPi devices with the black PiBridge plug connector on the top of the housings.

▷ Connect the power supply to the RevPi base module.

▷ Connect the power supply to the expansion modules via the X4 connectors.

▷ Connect the power supply for sensors and actuators to the inputs and outputs of the expansion modules.

❯ The PiBridge connection is established automatically.

After Connecting the Power Supply #

  • The piControl driver automatically recognizes all connected devices.

  • The configuration is loaded from the PiCtory configuration file.

  • Devices that are not configured are ignored.

  • Once all devices have been detected, the bus termination is activated on the last device and cyclical communication is started.

revpi-pibridge-assembly

PiBridge Communication #

The PiBridge provides two communication channels:

  • RS485 for RevPi I/O devices

  • Ethernet for RevPi Gateways

A maximum of one gateway can be connected per side. See also Rules for the Arrangement of Devices.

Pin Assignment #

The PiBridge uses a 20-pin plug connector to connect the devices. The bus is controlled by the connected devices.

The PiBridge provides a connector on both sides of a device for connection to neighboring devices. The signal assignment depends on the side.

Pin Assignment Left Side

Signal Description

LS

Control line for device release (Link Side Select)

L_SACK

Status/confirmation signal of the device

GND

Ground

LRX-

Ethernet RX

LRX-

Ethernet RX

LTX-

Ethernet TX

LTX+

Ethernet TX

GND

Ground

RS485

RS485 data line

RS485-

RS485 data line

Pin Assignment Right Side

Signal Description

RS

Control line for device release (Right Side Select)

R_SACK

Status/confirmation signal of the device

GND

Ground

RRX-

Ethernet RX

RRX+

Ethernet RX

RTX-

Ethernet TX

RTX-

Ethernet TX

GND

Ground

RS485

RS485 data line

RS485-

RS485 data line

Further Resources #